LightningController Compact - MCF50

Item no. 5096979 | EAN 4012197477028

5096979 / MCF50-3+NPE+FS
3+N/PE
12.5 kA
yes
255 V
IP20
Product description
Product description
Combination arrester, lightning current and surge protection arrester type 1+2+3

• Protection level < 2.5 kV
• For lightning protection equipotential bonding according to VDE 0185-305 (IEC 62305)
• Lightning current arresting capacity 50 kA (10/350) 3+NPE
• Follow current quenching rating Ifi 50 kA, arrester pre-fuse up to 315 A gL/gG
• Complies with the requirements for the use in the pre-meter area according to VDE-AR-N 4100
• Encapsulated non-extinguishing spark gap arrester for the application in distributor housings.

Application: industrial plants and buildings with external lightning protection of the classes III to IV.
Compact protective device
  • 5-year warranty
  • Communautés Européennes, EC declaration of conformity according to EC directives
  • RoHS-conformant
  • 230/400 V system
  • Combination protection device made of type 1 and type 2
  • Transition from LPZ 0 to LPZ 2
  • Remote signalling
  • Halogen-free; without chlorine, fluorine and bromine
  • Installation electrotechnical expertise
Technical data

Technical data

Dimension 255V
Follow current quenching capacity (eff) [N-PE] 50 kA
Housing material surge protection components PA UL 94 V-0
Humidity, max. 95 %
Humidity, min. 5 %
Installation type DIN rail 35 mm
Lightning surge current (10/350 μs) 12,5 kA
Lightning surge current (10/350) 50 kA
Max. mains-side overcurrent protection 315 A
Maximum back-up fuse 315 A
Maximum continuous voltage (L-N) 255 V
Maximum continuous voltage (N-PE) 255 V
Maximum continuous voltage AC 255 V
Maximum discharge current (8/20 μs) 50 kA
Maximum discharge current (8/20 μs) [L-N] 50 kA
Maximum discharge current (8/20 μs) [N-PE] 100 kA
Network form TN-S, TT
Nominal discharge current (8/20 µs) 35 kA
Nominal discharge current (8/20 µs) [L-N] 35 kA
Nominal discharge current (8/20 µs) [N-PE] 100 kA
Nominal voltage AC (50/60 Hz) 230 V
Permitted temperature range, max. 80 °C
Permitted temperature range, min. -40 °C
Pole number 4
Pole version 3+N/PE
Protection level [L-N] ≤1,5
Protection rating IP20
Remote signalling yes
Response time <100 ns
ROHS-conformant Exempt
Short-circuit resistance for max. mains-side overcurrent protection 50 kA eff
Signalling on device Visual
SPD to EN 61643-11 Type 1+2+3
SPD to IEC 61643-11 Class I+II+III
SPD to UL 1449 Type 4
Switching power AC 250V/ 1,5A
Switching power DC 250V/ 0,1A
TN network form yes
TN-C network form no
TN-C-S network form yes
TN-S network form yes
Torque 5 Nm
TOV voltage [L-N] ‒ fail safe mode ‒ 120 min. 442 V
TOV voltage [L-N] ‒ withstand mode ‒ 5 s 440 V
TOV voltage [N-PE] ‒ withstand mode ‒ 200 ms 1200 V
TT network form yes

Dimensions

Height 70 mm
Length 90 mm
Width 107 mm

Connectivity options

Arrester surge current (8/20 µs) [total] 50 kA
Combined voltage protection level [L-PE] 2,5 kV
Conductor cross-section, flexible (fine-wire), max. 3 AWG
Conductor cross-section, flexible (fine-wire), max. 25 mm²
Conductor cross-section, flexible (fine-wire), min. 1,5 mm²
Conductor cross-section, flexible (fine-wire), min. 16 AWG
Conductor cross-section, rigid (single-wire/multiwire), max. 35 mm²
Conductor cross-section, rigid (single-wire/multiwire), max. 2 AWG
Conductor cross-section, rigid (single-wire/multiwire), min. 1,5 mm²
Conductor cross-section, rigid (single-wire/multiwire), min. 16 AWG
Connection cross-section, FM terminals, max. 1,5 mm²
Connection cross-section, FM terminals, max. 16 AWG
Connection cross-section, FM terminals, min. 28 AWG
Connection cross-section, FM terminals, min. 0,5 mm²
FM contacts Changeover
All types

All types

Types Pole version Lightning surge current (10/350 μs) Remote signalling Maximum continuous voltage AC Protection rating Item no. Quantity SSU
MCF50-3+NPE+FS 3+N/PE 12.5 kA yes 255 V IP20 5096979
1 piece
Downloads

No invitation to tender text is available for this product.